IF08CZ10 April, 2019 - 16 -
General Specifications (Control)
The general (control) specifications are shown in the following table.
General Control Specifications
Item Standard specification Option Remarks
Maximum output frequency 75Hz
(66Hz for sync- transfer drives)
90Hz all non synch-
transfer drives
120Hz for most
4160V drives.
90Hz max with sine
wave filter, for
H4P, G4P, 2400V
& 6600V drives.
Speed sensor (PG pulse output) No Yes
Basic control
performance
Basic control
system
Induction Motor Volts/Hertz Induction Motor
Sensor Type Vector
Sensor type vector
control uses a 1x
resolver or a PG.
The maximum PG
freq. is 100kHz.
Induction Motor
Sensorless Vector
Synchronous Motor
Operation control
range
3%-100% 1%-100% Limited by motor
heating
Field weakening
control
1:1.5 1:5 Vector Control
Speed accuracy
±0.5% ±0.01%
Speed resolution 1/25000
(Digital setting)
Analog setting
1/1000. Isolation
transducer
recommended.
Acceleration/deceler
ation time
0.1 – 3276.7 sec,
acceleration/deceleration
independent setting
Most drives cannot
regenerate.
Operation
specification
Restart after
instantaneous
interruption
Possible
(more than 5 cycles interruption
causes shut down)
Under-voltage trip
at 75% level
Communicati
ons
Serial interface None MODBUS
DEVICE_NET
PROFIBUS
TL-S20
Requires optional
board.
Commissioning/Mai
ntenance Tool
Ethernet (with modular jack attached
to keypad)
Cubicle
display/
operation
LED 1 lamp
READY: Operation preparation
completed(Green)
RUN: Inverter in operation(Red)
ALARM/FAULT:
Alarm slow flashing/Fault fast flashing
READY and RUN
light colors can be
reversed by changing
an EOI parameter
LED 2 lamp
ON - Keypad control
OFF - Other than keypad control
LCD display 128x64 Pixel Graphical LCD display
Operation apparatus Backlit type interlock switch: 1
Unlit reset switch: 1
Operation via 8 key keypad and a
15pulse/30detent incremental
encoder
Connector Personal computer connection
Ethernet modular jack