IF08CZ10 April, 2019  - 57 - 
DRIVE INSTALLATION DRAWINGS (cont’d) 
Frame 0 4160V module lifting and installation 
 
WARNINGS
Disconnect power and wait 15 
minutes to ensure capacitors are 
discharged before performing 
inspection or maintenance. 
Improper handling of the fiber 
optic cables and connectors may 
cause drive failure due to 
problems transmitting signals.
Take care not to disturb fiber 
optic cables when handling 
power module.
Use module lifting attachment 
GCI6720G055 and a lifting device 
rated 250 lbs minimum for 
removal and installation of 
modules.
Power Module Removal
1.  Disconnect and remove AC
     neutral bus. 
2.  Disconnect power cables
     ACL, P, C & N.
3.  Remove control wiring
     cover (two  "A" bolts) 
4.  Disconnect control signal
     cable and 120VAC supply
     cable from module.
5.  Free slide tray by
     removing bolt "B".
6.  Pull slide tray out until
     slides lock.
7.  Remove four "C" bolts
     which secure module to
     tray.
Power Module Installation
1.  Pull slide tray out until
     slides lock.
2.  Using module lifting
     attachment and lifter, place
     module on tray. 
3.  Secure module to tray with
     four "C" bolts.
4.  Press slide release buttons
     and slide module into
     compartment (use caution).
5.  Reinstall bolt "B" to
     secure tray in position.
6.  Reconnect control signal
     cable and 120VAC supply
     cable to module
     connectors.
7.  Reinstall control wiring
     cover and secure with two
     "A" bolts.
8.  Reconnect power cables
     ACL, P, C & N.
9.  Reinstall AC neutral bus.
10. Torque all power
     connections (5/16-18 hdwr)
     to 10-15 ft-lbs.
Power Module Removal 
(cont'd)
8.  Using module lifting
     attachment and lifter,
     lift module from tray.
A
A
B
C
C
C
C
AC NEUTRAL BUS
 PINCH AREA
USE CAUTION
 PINCH AREA
USE CAUTION
CONTROL WIRING
COVER
LIFTING ATTACHMENT
LIFT HERE
N
C
P
ACN
ACL
CONTROL SIGNAL &
120VAC CABLES
PRESS BUTTON
(INSIDE OF DRAWER)
TO SLIDE TRAY BACK
PRESS BUTTON
(INSIDE OF DRAWER)
TO SLIDE TRAY BACK
 
 
Frame 0 2400V module lifting and installation 
 
WARNINGS
Disconnect power and wait 15
minutes to ensure capacitors are
discharged before performing
inspection or maintenance.
Improper handling of the fiber
optic cables and connectors may
cause drive failure due to
problems transmitting signals.
Take care not to disturb fiber
optic cables when handling
power module.
Use module lifting attachment
GCI6720G055 and a lifting device
rated 250 lbs minimum for
removal and installation of
modules.
A
A
B
C
C
C
C
 PINCH AREA
USE CAUTION
 PINCH AREA
USE CAUTION
CONTROL WIRING
COVER
LIFTING ATTACHMENT
LIFT HERE
N
C
P
ACL
CONTROL SIGNAL &
120VAC CABLES
PRESS BUTTON
(INSIDE OF DRAWER)
TO SLIDE TRAY BACK
PRESS BUTTON
(INSIDE OF DRAWER)
TO SLIDE TRAY BACK
BUS BAR (3)
Power Module Removal
1.  Disconnect power cables
     ACL, P, C & N (P, C & N on
     right-hand module only).
2.  Disconnect and remove bus
     bars P, C & N.
3.  Remove control wiring
     cover (two  "A" bolts)
4.  Disconnect control signal
     cable and 120VAC supply
     cable from module.
5.  Free slide tray by
     removing bolt "B".
6.  Pull slide tray out until
     slides lock.
Power Module Installation
1.  Pull slide tray out until
     slides lock.
2.  Using module lifting
     attachment and lifter, place
     module on tray.
3.  Secure module to tray with
     four "C" bolts.
4.  Press slide release buttons
     and slide module into
     compartment (use caution).
5.  Reinstall bolt "B" to
     secure tray in position.
6.  Reconnect control signal
     cable and 120VAC supply
     cable to module
     connectors.
7.  Reinstall control wiring
     cover and secure with two
     "A" bolts.
8.  Reinstall bus bars P, C & N.
9.  Reconnect power cables
     ACL, P, C & N (P, C & N on
     right-hand module only).
10. Torque all power
     connections (5/16-18 hdwr)
     to 10-15 ft-lbs.