IF08CZ10 April, 2019 - 23 -
Item
Abbreviation
Hardware
Detection
Software
Detection
Heavy Fault
Medium
Fault
Light
Fault
Start
Interlock
Coast
to stop
Decel
stop
Stop
request
Alarm
Overload alarm OL_A,OL_A_B O O
Overload (5 minutes) OL5, OL5_B O O
Overload (20 minutes) OL20, OL20_B O O
Over speed OSS O O*
Output frequency high OSS_F0 O O*
DC bus over-voltage positive/negative
OV_xP
OV_xN
O O*
Panel safety switch P_SW O O
Emergency Stop by Keypad DSP_ESTP O O
Parameter setting error PARA_ERR O O
PLL phase error PHASE_ERR O O
PLD error PLD_ERR O O*
Pre-charge CTT trip PRE_CTT O O
Pre-charge CTT alarm PRE_CTT_F O O O
DC Bus Charging Failure REC_F O O
Rectifier failure FUSE O O*
Reverse rotation failure REV_ROT_F O O*
Rotation/start failure ROT_F O O*
Soft stall SOFT_STL O
Analog Input Fault AIN_FAULT O O* O
Speed feedback error SP_ERR O O*
Speed feedback error2 SP_ERR2 O O*
Speed reference lost SP_LOST O O O
Speed reference lost alarm SP_LST_A O O O
Motor turning start interlock SP_SIL O
Spare input 1-4 SPA1-4 O O* O O
Spare input 1-4 timer SPA1-4_T O O* O O
System configuration error SYS_ERR O O
Communication error 1-4 TL_F1-4 O O O
Main under-voltage UV_MPSF O O
AC main voltage drop UVA_SIL
DC under-voltage start interlock UV_SIL O O O
DC under-voltage trip UVD, UVD_B O O
External equipment electrical ready condition UVA_EX O O
External safety switch UVS O O
Input voltage phase loss VAC_PH_LOSS O O
Input Voltage Phase Rotation Error VAC_ROT_F O O
Converter Input Phase Lost
VCNV_PH_LOSS
_
O O
Output current phase loss VINV_PH_LOSS O O
Inverter output voltage PLL error VPLL_ERR_ O O
Transfer Failure XFR_FAIL O O
Transfer Incomplete Sequence XFR_INCMP O
Capture Failure CPT_FAIL O
Stator Over Voltage OV_S O O*
Field Current Limit Timer FCL_T O O*
Field Current Limit Timer Alarm FCL_TA_ O O
Exciter Failure (Exciter Detection) FL_FAULT_ O O*
Instantaneous Field Overcurrent (Exciter
Detection) FOC
O O*
Instantaneous Field Overcurrent FOC_S O O*
Exciter Stopped while Running FSTOP O O*
Field Current Lost LF O O*
Limit Fault Reset LMT_FRST O O*
(Note 1) Hardware Detection: Items for which all IGBTs are directly turned off by hardware. Software Detection: Items for which the
protective interlock operation is performed by detecting errors, via software.
(Note 2) "O" marks in the interlock operation fields can be selected by parameter setting.
"*" indicates that the equipment outputs the trip signal to the input main circuit breaker.
“x” indicates the phase (U,V,W).