IF08CZ10 April, 2019 - 31 -
Digital Input
A total of 10 programmable digital inputs (DI1 to DI10) are provided. DI1-2 are capable of accepting
an external voltage input (24VDC). DI3-10 are internally connected to the drive’s internal 24VDC power
supply and should only be connected to dry contacts. These input signals can be individually assigned to
bits in the DI_EX1~7 and DIEX9~11 words. The available input assignments are shown below. For more
detail refer to the parameter setting manual.
Digital Input Options
BIT DI_EX1 DI_EX2 DI_EX3 DI_EX4 DI_EX5
F IL_ N.U. QSTOP N.U. JOG3
E UVS N.U. UVS SPA0 JOG2
D EXT0 N.U. EXT0 FLD JOG1
C SPA1 SPA4 CM_BUF1 B JOG0
B BRTST SPA3 CM_BUF2 SC_PPI EX_LMT_I1
A ST SPA2 ST 2S EX_LMT_TR
9 F BLA_ F 3S SP_UP
8 R M_FN_ R R_TEN SP_DN
7 3S OH_ACL_EX_ 3S ST SEL_DI
6 2S E_DRIVE 2S LB DIR0
5 B HOLD N.U. N.U. DIR1
4 FLD QSTOP FLD BC_ START0
3 BC_ F_LMT_ LATCH_PG_POS N.U. START1
2 SPA0 R_LMT_ SPA0 UVS STOP0
1 EXRST B_HLTY EXRST EXT0 STOP1
0 R_TEN BA R_TEN EXRST EXT1
BIT DI_EX6 DI_EX7 DI_EX9 DI_EX10 DI_EX11
F N.U. N.U. MP_BE_TM_H1_ MP_BR01_CL MP_OL_TM_A_
E N.U. N.U. MP_BE_TM_H2_ MP_BR02_CL MP_OL_TM_TR_
D PR_ST N.U. MP_BE_TM_H3_ MP_BR03_CL MP_WD_TM_A_
C RATE_CHG F MP_CF1_MR MP_BR04_CL MP_WD_TM_TR_
B FL_FOC R MP_CF2_MR MP_BR05_CL MP_OL_LVL_A_
A FL_READY N.U. MP_CF1_MCC_F_ MP_BR06_CL MP_OL_LVL_TR_
9 FL_RNTD R_TEN MP_CF2_MCC_F_ MP_BR07_CL MP_PRD_A_
8 FL_FAULT N.U. MP_CWF_L1_ MP_BR08_CL MP_PRD_TR_
7 CHG_2S EXRST MP_CW_TM_H1_ MP_BR09_CL MP_BH_RL_A_
6 SEL_MRH 3S MP_OLU_LFD_ MP_BR10_CL MP_BH_RL_TR_
5 ASD 2S MP_OLU_HFD_ MP_WLK1_ MP_GP_RL_TR_
4 IM_NUM_B1 B MP_OLU_HPL_N MP_CF_IL_ N.U.
3 IM_NUM_B0 EXT0 MP_OLU_LPL_N MP_SPH_IL_ N.U.
2 XFR_CHK QSTOP MP_SPH_ON MP_OL_P_IL_ N.U.
1 CPT IL MP_SPH_MCC_F_ N.U. N.U.
0 XFR UVS MP_SW_TM_H_ N.U. N.U.