IF08CZ10 April, 2019  - 36 - 
 
INTERFACE (cont’d) 
 
[Setting examples] 
 
Example 1: 
 Analog speed reference is input to AIN1. 
 
Set 0 to 100% (0 to 1.0) speed reference signal at 0 to +10 V so that it is stored in SP_REF1. 
Use a personal computer with the maintenance tool installed for setting the parameters. 
The input characteristic is shown in the following figure. 
AIN1_TYPE = 1 
AIN1_OS = 0 
AIN1_AS = SP_REF_AIN1 
AIN1_GS = (1.0 / 10 V) x 10 V 
                = 1.0 
 
 
 
Input Characteristic Example 
 
 Example 2  When a 4~20 mA (0 to 100%) speed reference is input to AIN1, it is recommended 
that a 4-20 mA / 0-10 VDC transducer be used.   If the source is isolated, an internal 510 Ohm 
burden resistor may also be used via a jumper on the brd..  This would give 2VDC at 4mA.  In this 
case, an offset would need to be set in the drive as follows:  
 
AIN1_GS  = 2 / (20mA - 4mA) x 20mA = 2.5 
AIN1_OS  = -2.5 x 4mA / 20mA = -0.5 
AIN1_AS = SP_REF_AIN1 
AIN1_TYPE = 1