Series Digital Solid State Soft Starter User Manual        6 | Page
 
 
2.4   SERVICE WARNING! 
Do not service equipment with voltage applied! The unit can be the 
source of fatal electrical shocks! To avoid shock hazard, 
disconnect main power and control power before working on the 
unit. Warning labels must be attached to terminals, enclosure and 
control panel to meet local codes. Use Lockout tags such as the 
one shown when servicing equipment. 
 
2.5   Mounting and Cleaning 
When drilling or punching holes in the enclosure, cover the electrical 
assembly to prevent metal filings from becoming lodged in areas which 
can cause clearance reduction or actual electrical shorts. After work is 
complete, thoroughly clean, vacuum the area, and re-inspect the unit for 
foreign material.  
2.5.1  Clearances 
Make sure there is sufficient clearance all around the unit for cooling, 
wiring, and maintenance purposes. To conserve panel space, the TE2 
Series - BP models were designed for close clearances of only 1 inch 
(25mm) on either side. A minimum clearance of 4 inches (100 mm) on 
the top and bottom is necessary to maximize effective airflow and 
cooling. Also the unit must be installed with its heat sink ribs oriented 
vertically and running parallel to the mounting surface. Keep in mind 
that these are minimums. NEC or local codes may require more 
clearance, particularly for the power terminals. 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
                        Figure 2.5:  TE2 minimum mounting clearances 
TE2  Series
Starte
1" minimum (25  mm )
1" minimum (25  mm )
4" minimum ( 100 mm )
4" minimum ( 100 mm )