5.5 The TE2 Function List
5.5.1 Motor FLA, Service Factor and Overload Protection
Functions
5.5.2 Starting Mode Functions
Fn # Group Function Description Adjustment / Display Range
Setting
Increments
Factory
Setting
Section
F001
Motor and Overload Info.
Motor Nameplate FLA
FLA must be programmed for
starter to function.
50 -100% of Max Amp Rating.
Upper limit of range automatically
adjusts downward as Service factor
is increased.
1 amp 0
5.6.1
and
3.2
F002
Motor Nameplate
Service Factor
1.00 - 1.30 SF 0.05 1.0 SF
F003 Overload Class During Start NEMA / UL Class 5 -30 5 Class 10
F004 Overload Class During Run NEMA / UL Class 5 - 30 5 Class 10
F005 Overload Reset
0 = Manual
1 = Auto
2 = Disabled Overload
1
0
(Manual)
F006
-
F009
Reserved for factory use
Table 5.5.1: Motor and Overload Function Group
Fn # Group Function Description Adjustment / Display Range
Setting
Increments
Factory
Setting
Section
F010
Starting and Stopping Modes
Ramp Type Selection:
VR = Voltage Ramp
CR = Current PID Ramp
1 = Ramp 1, 2 = Ramp 2
Setting 1 = VR1 + VR2
Setting 2 = CR1 + CR2
Setting 3 = VR1 + CR2
Setting 4 = CR1 + VR2
1
1
VR1+VR2
5.6.2
and
Append.
1
F011 Initial Torque (VR) of Ramp 1 0 - 100% Line Voltage 1% 60%
F012 Initial Torque (CR) of Ramp 1 0 - 600% Motor
Current
1% 200%
F013 Accel Ramp Time of Ramp 1 1 - 120 seconds 1 second
10
seconds
F014 Max Current Limit of Ramp 1 200 - 600% Motor
Current
1% 350%
F015 Initial Torque (VR) of Ramp 2 0 - 100% Line Voltage 1% 60%
5.6.2,
Append.
1
and
4.2.5
F016 Initial Torque (CR) of Ramp 2 0 - 600% Motor
Current
1% 200%
F017 Accel Ramp Time of Ramp 2 1 - 120 seconds 1 second
10
seconds
F018 Max Current Limit of Ramp 2 200 - 600% Motor
Current
1% 350%
Table 5.5.2: Starting Mode Function Group