TE2 Series Digital Solid State Soft Starter User Manual       41 | Page 
 
  5.6.2.a      Ramp 2 (user-optional ramp) 
 
This ramp is selected by closing the input for Ramp 2, TB1 - 
terminals 5 & 6 (see section 4.2.5). If this input is left open, the TE2 
Series will respond only to Ramp 1 settings as listed above. Since 
ramp 2 is always used as an alternate to the default Ramp 1, 
different combinations of ramp profiles can be selected in F010. 
Refer to Appendix 1 for additional information on ramp profiles. 
 
F015 =  Initial Voltage of Ramp 2 
Factory Setting = 60% 
Range = 0 - 100% 
Sets the initial voltage of Ramp 2 when F010 = 1 or 4. The 
initial voltage level should be set to provide just enough torque 
to make the motor shaft begin to rotate while preventing torque 
shock damage to mechanical components. 
 
F016 =  Initial Current of Ramp 2 
Factory Setting = 200% 
Range = 0 - 600% 
Sets the initial current of Ramp 2 when F010 = 2 or 3. The 
initial current level should be set to provide just enough torque 
to make the motor shaft begin to rotate while preventing torque 
shock damage to mechanical components. 
 
F017 =  Accel Ramp Time of Ramp 2 
Factory Setting = 10 seconds 
Range = 1 - 120 seconds 
Sets the time between the initial value set with F015 or F016 
and either the Max Current Limit set with F018 or full output 
voltage. Also consider the motor’s application. For example, 
centrifugal pumps may require a shorter time. See notes for 
F013 for more details. 
 
F018 =  Max Current Limit of Ramp 2 
Factory Setting = 350% 
Range = 200 - 600% 
Sets the maximum motor current that the TE2 Series starter will 
allow during Ramp 2. (This limit applies to both voltage and 
current-type ramping.) The current will be limited to this setting 
until either the motor reaches full speed or the overload 
protection feature trips (F003).  
 
  Note: 
Ramp 2 is often useful as a “bump start” or as a temporary Across-
the-Line start mode. Consult Appendix 1 for details.