TE2 Series Digital Solid State Soft Starter User Manual 84 | Page
Appendix 5 - Soft Starter Settings Record
The following chart may be used to record the changes made to the factory settings.
Fn # Group Function Description Adjustment / Display Range
Setting
Increments
Factory
Setting
Setting
F001
Motor and Overload Info.
Motor Nameplate FLA
FLA must be programmed for
starter to function.
50 - 100% of Max Amp Rating.
Upper limit of range
automatically adjusts downward
as Service factor is increased.
1 amp 0
F002
Motor Nameplate
Service Factor
1.00 - 1.30 SF 0.05 1.0 SF
F003 Overload Class During Start NEMA / UL Class 5 - 20 5 Class 10
F004 Overload Class During Run NEMA / UL Class 5 - 30 5 Class 10
F005 Overload Reset
0 = Manual
1 = Auto
2 = Disabled Overload
1
0
(Manual)
F006
-
F009
Reserved for factory use
Fn # Group Function Description Adjustment / Display Range
Setting
Increments
Factory
Setting
Setting
F010
Starting and Stopping Modes
Ramp Type Selection:
VR = Voltage Ramp
CR = Current PID Ramp
1 = Ramp 1, 2 = Ramp 2
Setting 1 = VR1 + VR2
Setting 2 = CR1 + CR2
Setting 3 = VR1 + CR2
Setting 4 = CR1 + VR2
1
1
VR1+VR2
F011 Initial Torque (VR) of Ramp 1 0 - 100% Line Voltage 1% 60%
F012 Initial Torque (CR) of Ramp 1 0 - 600% Motor
Current
1% 200%
F013 Accel Ramp Time of Ramp 1 1 - 120 seconds 1 second
10
seconds
F014 Max Current Limit of Ramp 1 200 - 600% Motor
Current
1% 350%
F015 Initial Torque (VR) of Ramp 2 0 - 100% Line Voltage 1% 60%
F016 Initial Torque (CR) of Ramp 2 0 - 600% Motor
Current
1% 200%
F017 Accel Ramp Time of Ramp 2 1 - 120 seconds 1 second
10
seconds
F018 Max Current Limit of Ramp 2 200 - 600% Motor
Current
1% 350%