TE2 Series Digital Solid State Soft Starter User Manual       60 | Page 
 
5.6.14   Phase Protection Settings 
 
F098 =  Phase Rotation Trip 
Factory Setting = 0 (Disabled) 
Range = 0 (Disabled), 1 (A-B-C), or 2 (B-A-C) 
The TE2 Series is set up to monitor an expected Phase 
Rotation and trip if it changes. Control of this is divided into two 
categories: Enable or Disabled and Expected Sequence. The 
default setting is disabled. 
 
Setting this function to disabled (setting 0) is useful in 
applications where the TE2 Series is going to be used 
downstream from an existing reversing contactor or to avoid 
conflicts with other protection devices.  
On large motors where large multiple conductors are used, it 
may be easier to change the Expected Sequence in the TE2 
Series starter rather than swap the conductors. 
 
F099 =  Phase Rotation Trip Delay 
Factory Setting = 1 second 
Range = 1 - 20 seconds 
Provides a time delay to prevent nuisance trips from short-
duration transients. Using default settings, if the phase rotation 
is detected to be different for more than 1 second the starter will 
trip. 
 
F100 =  Phase Loss Trip Delay during Stop 
Factory Setting = 1 second 
Range = 0 - 20 seconds (0 = Disabled) 
Provides a time delay to prevent nuisance trips from short-
duration transients while stopped.  
Note: Based on loss of input voltage on one phase while 
decelerating or stopped. 
 
F101 =  Phase Loss Trip Delay during Running 
Factory Setting = 1 second 
Range = 0 - 20 seconds (0 = Disabled) 
Provides a time delay to prevent nuisance trips from short-
duration transients while running.  
Note: Based on current in one phase dropping below 20% of 
FLA (F001), while starting or running.