TE2 Series Digital Solid State Soft Starter User Manual       59 | Page 
 
5.6.13.b Statistical Data 
 
F094 - F097 display information from the Run Time / Elapsed Time 
meter and Run-Cycle counter.  
 
Run Time includes Accel, Run, Decel, and Jog operations.  
 
Run Cycles are counted only when the starter reaches At-Speed mode. 
 
F094 =  Run Time, Hours 
Factory Setting = 0000 
Range = 000.9 - 999.9 hours 
Run times in excess of 999.9 are recorded in F095. 
F095 = Run Time, K Hours 
Factory Setting = 0000 
Range = 0000 - 9999 K hours 
0001 in readout means a run time of 1,000 hours. 
F096 = Run Counts 
Factory Setting = 0000 
Range = 0000 - 9999 
Run counts in excess of 9999 are recorded in F097. 
F097 = Run Counts, 10K Times 
Factory Setting = 0000 
Range = 0000 - 9999, 10 thousand times 
0001 in readout means a run count of 10,000 operations. 
 
 
 
 
 
 
 
 
 
 
  
Examples: 
Overflow 
Value  
Basic  
Value  
Run Time  
23,047 Hours 
F095  F094 
0002  3047 
Run Counts  
18,702 Starts 
F097  F096 
0001  8702 
Table 5.5.15:  Statistical Data Examples