TE2 Series Digital Solid State Soft Starter User Manual       56 | Page 
 
When F068 = 3, and the jog input is set to “Remote/Local” in 
F113 the TE2 starter will change the function of the Jog Input 
to cause a switch between the functions of setting 0 and setting 
1 as listed above. When the input is open, the starter will 
respond to the COM port as per setting F068=0. When the Jog 
Input is closed, the starter will respond as per setting F068=1. 
Use this function if it is necessary to have a return to local 
start/stop control should the communications system fail or 
become disconnected. NOTE: There is no jog function 
available, due to the reconfiguration of the jog input port. The 
jog input must be manually changed to “Remote/Local” in 
parameter F113. 
 
F069= Reserved 
 
5.6.12 System Settings 
 
The following functions set operator interface controls and unit 
programming. Also contained here are the Clock settings used for 
history functions. Change the Clock settings to local time zone if 
accurate time values are needed. 
 
F070 =  Parameter Lock / User Password 
Factory Setting = 0 (disabled) 
Range = 0 - 999 
Use only when necessary to prevent unauthorized access. 
Provides users with the ability to prevent unauthorized 
operators from making changes to the programmed functions.  
If you do NOT need to take advantage of this feature, do not 
enter anything into this function. The factory default is disabled, 
and no Password is necessary to make changes to the 
program. 
See Appendix 3 at the end of this manual for detailed instructions 
on using and altering the Parameter Lock / User Password 
feature. 
 
F071 =  Emergency Clear / Reset 
Factory Setting = 0 (disabled) 
Range = 0 - 2 
This Function serves two purposes. It can clear the memory 
values used for lockouts and overload protection, and it can 
reset all functions to the factory default settings. This is a “One-
Shot” feature, so when another value is entered as shown 
below, this function automatically returns to the default state. 
  When F071 = 0, the feature is disabled.  
  When F071 = 1, the values stored in the Thermal Register and all of 
the Lockout Timers will be cleared. This will allow an Emergency 
Restart without having to wait for proper cool down time or lockout 
timers to expire. 
WARNING! 
Clearing the Thermal Register to allow restarting without proper 
cool-down time after an Overload Trip can result in motor damag
e 
and fire. Use only where emergency restart is necessary with 
knowledge of these potential hazards.