TE2 Series Digital Solid State Soft Starter User Manual 25 | Page
5.4 Program Mode
The starter must be OFF (Motor Stopped) in order to enter the Program
Mode. Use the Program Mode to view or change Function (Fn) settings.
To enter the Program Mode, press the [Fn] key once from the Status
Screen described in 5.3.1 above. The first time you enter the Program
Mode after power has been cycled to the starter, the initial function
[F001] should be displayed with the selected digit flashing. If the TE2
Series starter has been programmed and power to the unit has not
been cycled, the readout will display the last function viewed or
changed. To change to a different function, use the arrow keys.
5.4.1 Viewing Function Programming and Values
While in the RUN Mode, the programming of each individual function
and metering values can be viewed, but no changes are allowed. Each
Function is signified by the letter "F" at the beginning of the data. The 4-
digit value of the function follows after pushing the (READ/ENTER) key.
[F001] The “F” indicates the programmable Function.
[0000] This is the present setting of the applicable function. This
display may include decimals between digits depending on the function
setting’s range and incremental steps.
Example: Figure 5.4.1
Viewing a Function’s Set Value:
Motor FLA Setting
[0000.] Indicates that Phase A is drawing no current
(unit is in Off mode).
Press the Fn key
[F001] Indicates that this is Function 001 (Motor FLA).
Press Read / Enter key
to view the F001’s value
[0306] Indicates that the programmed motor FLA is
360 Amps.
Press the Fn key
to return to the function
[F001] Indicates that you have returned to the Function
Select screen.
Press the Fn key again
to return to the Status Display Mode
[0000.] Indicates that Phase A is drawing no current
(unit is in Off mode).
Note:
If password protection has been enabled, the operator will need to
obtain password access before function settings can be changed.
See Section 5.6.12 and Appendix 3.
Display
Press
Key...
Shows...
Means...
Default Display:
Phase A Current
Selecting
Function #1
Fn 1 Value:
FLA = 360A
Return to
Default Display
Without Change
0000.
F001
0360
Figure 5.4.1:
View ing a Function's Set Value
0000.
Return to Function
# Selection
F0 0 1
READ
ENTER
Fn
Fn
Fn