TE2 Series Digital Solid State Soft Starter User Manual 64 | Page
5.6.17 Display & System Settings
F111 = Display Setting
Factory Setting = 10
Range = 1 - 12, 0 (Off)
Sets default display monitor
Value Display Definition
1
XXXX. (A) or
XX.XX. (kA)
Ia: Phase A Current (With a dot “.” Shown at bottom right corner
of rightmost digit.)
Shows XX.XX if Iavg>9999 Amp. e.g.12.50 means 12.5 kA.
2
XXXX (A) or
XX.XX (kA)
Ib: Phase B Current
Shows XX.XX if Iavg>9999 Amp.
3
XXXX (A) or
XX.XX (kA)
Ic: Phase C Current
Shows XX.XX if Iavg>9999 Amp.
4
GXXX Igf: Ground Fault Current
5
UXXX Uab: Line Voltage AB
6
UXXX Ubc: Line Voltage BC
7
UXXX Uca: Line Voltage CA
8
L
XXX (
L
is like superscript) or
L
XXX (
L
is like subscript)
Power Factor (A large L is for Lead and a small L is for lag).
Either of them is shown at leftmost digit)
9
PXXX
KW (w/o decimal point) or MW (w/ decimal point):
Kilo-watt (range: 000 - 999);
Mega-watt (range: 0.00 - 9.99)
10
XXXX (A) or
XX.XX (kA)
Iavg: Average of 3 Phase Currents (It is factory default display);
Shows XX.XX if Iavg>9999 Amp.
11
UXXX Uavg: Average of 3 Line Voltages
12
HXXX Thermal Capacity Remaining
F112 = System Settings - Reserved
F113 = Alternate functions for Ramp2/Jog inputs
Factory Setting = 7
Range = 0 - 7
Sets system settings.
Quick Setup of F113:
Data Dual Ramp Input Jog Input
0 Dual Ramp Jog
1 Dual Ramp Remote / Local
2 Dual Ramp Ext. Lockout N/O button
3 Dual Ramp Ext. Lockout N/C button
4 RESET Jog
5 RESET Remote / Local
6 RESET Ext. Lockout N/O button
7 RESET Ext. Lockout N/C button
Note: When Jog Input is set to
“Remote/Local”, “Remote” is
communication as set in F068,
and “Local” is normal control via
the terminal strip.