TE2 Series Digital Solid State Soft Starter User Manual 63 | Page
F109 = Analog Output 4mA
Factory Setting = 0
Range = 0 - 9999
Enter a value that the 4mA level will represent for the selected
function; typically this value should be 0.
F110 = Analog Output 20mA
Factory Setting = 9999
Range = 0 - 9999
Enter a value that the 20mA level will represent for the selected
function.
Example: Use Analog Output to measure Line Voltage AB
Set F108 to 3 (Line Voltage AB)
Set F109 to 0
Set F110 to 480