TE2 Series Digital Solid State Soft Starter User Manual 31 | Page
5.5.3 Jog Mode Functions
5.5.4 Kick Start Mode Functions
5.5.5 Decel Mode Functions
5.5.6 Restart Function
Fn # Group Function Description Adjustment / Display Range
Setting
Increments
Factory
Setting
Section
F019
Jog Modes
Voltage Jog 5 - 100% Line Voltage 1% 50%
5.6.3
and
4.2.5.b
F020 Time of Voltage Jog 1 - 20 Seconds 1 second
10
seconds
F021 Current Jog 100 - 500% Motor
Current 1% 150%
Table 5.5.3: Jog Mode Function Group
Fn # Group Function Description Adjustment / Display Range
Setting
Increments
Factory
Setting
Section
F022
Kick Mode
Kick Start Voltage
0 = Disabled, or
10 - 100% Line Voltage
1%
0
Disabled
5.6.4
F023 Kick Start Time 0.1 - 2 Seconds 0.1second
0.8
seconds
Table 5.5.4: Kick Start Mode Function Group
Fn # Group Function Description Adjustment / Display Range
Setting
Increments
Factory
Setting
Section
F024
Pump Flex Decel Mode
Pump Flex Control /
Deceleration Ramp
0 = Disabled (coast to stop)
1 = Enabled, Power OFF on OL trip
2 = Enabled, Decel even
if there is an OL trip
1
0
Disabled
5.6.5
and
Append.
2
F025
Begin Decel Level (BDL),
Immediate Drop Down Torque
0 - 100 % of Output Voltage 1% 60%
F026 Decel Shut Off Voltage 0 to (BDL minus 1)% Voltage 1% 30%
F027 Decel Ramp Time 1 - 60 Seconds 1 second
10
seconds
Table 5.5.5: Pump Flex Decel Mode Function Group
Fn # Group Function Description Adjustment / Display Range
Setting
Increments
Factory
Setting
Section
F028
Restart
Auto Restart Delay Time
(Sequential Start Delay)
0 = Disabled, or
1-999 seconds after a Power Loss
(Status can be read in F054)
1 second
0
Disabled
5.6.6
Table 5.5.6: Restart Function Group