TE2 Series Digital Solid State Soft Starter User Manual 29 | Page
5.4.5.c Automatic Reset
The TE2 Series starter provides for automatic reset on certain non-
critical faults and Overload. For non-critical fault resets, see section
5.6.9.b for program details of F052. For automatic Overload reset,
see section 3.1.3.b and 5.6.1 for programming details.
5.4.5.d Lockout Functions
Lockout functions such as Minimum Time Between Starts and
Starts per Hour are not true fault conditions. They are based on the
internal Real Time Clock (RTC). When control power is removed,
the RTC value is quickly stored. Upon return of power, the timer
values are updated from the RTC for elapsed time. If the Lockout
Time has not expired, the TE2 Series cannot be started. To reset
the Lockout Times for emergency restart, see section 5.6.11, under
F071.
5.4.5.e Changing to Default Screen During Fault
In some cases, it may be necessary to alter programmed
parameters in order to test or make changes to clear a fault (such
as Phase Loss), or to view the more detailed fault history in F085 -
F097. To accomplish this, you must get to the Status Screen so the
Fn button becomes active. When in a Fault Screen, pressing the
Right or Left Arrow buttons will take you to the Status Screen. From
there, you can press the [Fn] key to enter the Programming Mode
and move to different functions.