TE2
Series Digital Solid State Soft Starter User Manual 82 | Page
Appendix 4 (cont.) External OL Relay Applications
SPECIAL MOTOR APPLICATIONS
Multiple Motors
When more than one motor is connected downstream from the TE2
Series starter, the internal electronic overload protection cannot provide
proper protection of the individual motors. Codes require the use of
separate OLRs for each motor, which would need to be external
devices.
In these instances the TE2 Series Overload protection should be turned
off, deferring protection to the separate OLRs. Care should be taken to
ensure that the External OLR is properly wired into the starter control
circuit to facilitate shutdown of the motor.
TE Starte
.
Bypass
Contactor
"BP"
Disconnect
o
Circuit
Breake
Solid State
.
Over Loa
.
MTR
1
G
R /
L1
T
L3
S /
L2
U /
T1
W /
T3
V /
T2
Externa
Over Load 1
1 2 3
A1 A2
120VAC CONTROL POWER
Start / Run
Command
TE2...-BP Series
Control Wiring
TE2-TB-1
(24VDC)
TE2-TB-2
MTR
2
Externa
Over Load 2
4
5
TE2-TB-1
(NC Input )
External
OL 1
External
OL 2