E6581818
- 10 -
Title
Communi
cation No.
Function Description Default
c021 C021 Scanner output 1 address
0: None
1: fd01 (Inverter status 1)
2: fd00 (Output frequency, 0.01Hz)
3: fd03 (Output current, 0.01%)
4: fd05 (Output voltage, 0.01%)
5: fc91 (Inverter alarm)
6: fd22 (PID feedback value, 0.01Hz)
7: fd06 (Input terminal status)
8: fd07 (Output terminal status)
9: fe36 (VIB input, 0.01%)
10: fe35 (VIA input, 0.01%)
11: fe37 (VIC input, 0.01%)
12: fd04 (Input voltage (DC detection), 0.01%)
13: fd16 (Estimated speed
(real-time value), 0.01Hz)
14: fd18 (Torque, 0.01%)
19: f880 (Free notes)
20: fd29 (Input power, 0.01kW)
21: fd30 (Output power, 0.01kW)
22: fe14 (Cumulative operation time,
0.01 = 1 hour)
23: fe40 (FM terminal output monitor, 0.01%)
25: fd20 (Torque current, 0.01%)
26: fd23 (Motor overload factor, 0.01%)
27: fd24 (Drive overload factor, 0.01%)
28: fd25 (PBR overload factor, %)
29: fd26 (Motor load factor, %)
30: fd27 (Drive load factor, %)
31: fe56 (Pulse train input, pps)
32: fe70 (Drive rated current, 0.1A)
33: fe76 (Input Watt-hour, 1kWh 10
f749
)
34: fe77 (Output Watt-hour, 1kWh 10
f749
)
35: fd83 (IGBT temperature, degree C)
100: ETA
101: RFRD
100*
2
*
3
c022 C022 Scanner output 2 address 0-101 (Same as c021) 101*
2
*
3
c023 C023 Scanner output 3 address 0-101 (Same as c021) -*
2
*
3
c024 C024 Scanner output 4 address 0-101 (Same as c021) -*
2
*
3
c025 C025 Scanner output 5 address 0-101 (Same as c021) -*
2
*
3
c026 C026 Scanner output 6 address 0-101 (Same as c021) -*
2
*
3
c041 C041 Scanner input 1 value The argument value set to c001 is displayed. -*
3
c042 C042 Scanner input 2 value The argument value set to c002 is displayed. -*
3
c043 C043 Scanner input 3 value The argument value set to c003 is displayed. -*
3
c044 C044 Scanner input 4 value The argument value set to c004 is displayed. -*
3
c045 C045 Scanner input 5 value The argument value set to c005 is displayed. -*
3
c046 C046 Scanner input 6 value The argument value set to c006 is displayed. -*
3
c061 C061 Scanner output 1 value The argument value set to c021 is displayed. -*
3
c062 C062 Scanner output 2 value The argument value set to c022 is displayed. -*
3
c063 C063 Scanner output 3 value The argument value set to c023 is displayed. -*
3
c064 C064 Scanner output 4 value The argument value set to c024 is displayed. -*
3
c065 C065 Scanner output 5 value The argument value set to c025 is displayed. -*
3
c066 C066 Scanner output 6 value The argument value set to c026 is displayed. -*
3
c100 C100
Communication error
detection delay time
0.0 - 100.0 sec. 0.1<
c101 C101
Inverter operation at the
communication loss action
0: Stop and controlled by cmod, fmod
1: Operation continue
2: Deceleration stop
3: Coast stop
4: Network error stop (err8 trip)
5: Preset speed operation (by c102 setting)
-
c102 C102
Preset speed
operation selection
0: None
1 to 15: Preset speed
-