Printed in the Federal Republic of Germany TR-Electronic GmbH 2020, All Rights Reserved
10/07/2020 TR-ECE-BA-GB-0163 v03 Page 15 of 91
● The measuring system status LEDs are not reliable indicators and no guarantee can be given that
they will provide accurate information. LEDs may thus only be used for the purpose of general
diagnosis during commissioning or troubleshooting but may not be used as an operational display.
See Chapter 4.3 on Page 34.
● The automatic SNN setting function of originator devices may only be used if the safety system
does not rely on it. See Chapter 3.5.2 on Page 30.
● The measuring system must always be locked after the configuration data have been verified. See
Chapter 4.5 from Page 36.
● As part of the final verification process, users must verify that the measuring system has received
its ownership assignment from the relevant originator if the measurement system has been
configured via a Type 1 SafetyOpen.
● Visually verify that all configuration data have been correctly downloaded to the measuring
system. See Chapter 4.5 from Page 36.
The measuring system cannot receive configuration data
from another originator in
the presence of an ownership assignment by another originator. In this case you
must reset the measuring system to remove the ownership assignment. See Chapter
“Resetting the safety-related device parameters“ on Page 39.