Printed in the Federal Republic of Germany TR-Electronic GmbH 2020, All Rights Reserved
10/07/2020 TR-ECE-BA-GB-0163 v03 Page 31 of 91
Ensure the correct measuring system has been programmed with the preset SNN before writing the
SNN. Use one of the following verification options found under the program tab Device ID:
Displayed article number and serial number in the field Device ID and MAC address displayed in the
field MAC address. These data are noted on the nameplate of the measuring system.
The button Identify triggers the status LEDs of the relevant measuring system to flash, which
makes assignments simple and easy.
Execute the function Apply after verifying that the correct measuring system has being addressed.
The measuring system immediately applies these settings.
Several devices can be integrated into the LAN network via a switch if several devices have to be
programmed. Select the devices by entering the corresponding IP address in the TR SNCT Device
Applet.
Originators that support Type 1 SafetyOpen configurations can also program the
TUNID. These originator devices support the “SNCT-to-Originator-to-Target”
configuration scheme.
The user must ensure the uniqueness of an automatically assigned SNN
originator programmed the TUNID with an automatic SNN setting function.