EasyManua.ls Logo

Trane CCEB - Page 44

Trane CCEB
111 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Size
(of the cable gland)
External drilling diameter
(for screwing)
Internal drilling diameter
(for sleeve)
M 16
17
19
M 20
21
23
M 25
26
28
M 32
33
35
M 40
41
43
M 50
51
55
M 63
64
71
Table 3: Drilling diameters for cable glands
Figure 68: Step drill
3. Insert sleeve (inside see Figure 69) and screwing (outside see Figure 70) into the drillings
and screw them together (see Figure 71).
Figure 69: Sleeve
Figure 70: Screwing
Figure 71: Cable gland
A drilling with the diameter for the corresponding screwing (see Table 3, column 2) is sufficient for
the insertion of cables into a cabinet or a single walled housing. In this case the screw is locked
with the supplied locknut from the inside.
Transport lock
Remove the, on fan-motor base frame of spring isolators mounted transport lock (signed with red
point) according to Figure 72 below.
1. Remove nuts and bolts of position 1, 2 and 3
2. Remove z-shaped metal sheet (position 4)
3. Again fasten the nut of position 1, including the potential compensation wire