Operator Settings
Information Manual 21
Time Of Day Setting
The top level "CurrentTime/Date" will be displayed
when this screen is first selected. Pressing the
<Next> or <Previous> key will go to the next or
previous screen as usual.
If the <Enter> key is selected, five separate screens
can be displayed with which the time may be set. The
“Current Time/Date” will be displayed on line one of
each of these screens. Each of these screens will
change one element of the current time/date. The
second line of each screen will indicate which
element of the current time/date is being changed.
If the first time changing screen is being displayed
and the <Previous> key is pressed, the top level
“Current Time/Date” screen will be displayed and the
<Enter> key will have to be selected to re-enter the
time changing screens. If the fifth time changing
screen is being displayed and the <Next> key is
pressed, the next screen will be displayed. If
<Previous> is selected at this point, the top level
“Current Time/Date” screen will be displayed and the
<Enter> key will have to be selected to re-enter the
time changing screens
To change an element of the current time/date,
select <Enter> from the top level “Current Time/Date”
screen to enter the time changing screens. Hit
<Next> or <Previous> to get to the proper screen.
Press the <+> <-> keys to change the element to it's
proper value and press the <Enter> key to store the
new time/date. A message “Updating Chiller Clock,
Please Wait” is displayed for two seconds after the
<Enter> key is pressed.
The five time changing screens are as follows:
Front Panel Chilled Water Setpoint
Range of values is 0 to 65°F (-17.8 to 18.3°C) in
increments of 1 or 0.1°F or °C depending on the
Service Setup Screen xxx or xxx.x. Factory Default is
44.0°F (6.7°C).
As shown above, the second line of a setting display
normally says:
“Press (+)(-) to Change Setting”
However, the following is displayed as the second
line of the display if an attempt is made to increment
the setpoint above the end of the setpoint range:
“Top of Range, Press (-) to Change”
The following is displayed as the second line of the
display if an attempt is made to decrement the
display below the end of the setpoint range:
“Bottom of Range, Press (+) to Change”
The following is displayed as the second line of the
display if a key other than <+>, <->, <Enter>, or
<Cancel> is pressed after <+> or <-> is pressed:
“Press (+)(-)(Enter)(Cancel) to Advance”
The exception to the above message is when the
<Stop> key is pressed. <Stop> is always active.
Current Time/Date HH:MM xm Mon,XX XXXX
(Enter) to Change : (Next) to Continue
Current Time/Date HH:MM xm Mon XX,XXXX
To Change Hour, Press (+)(-) & (Enter)
Current Time/Date HH:MM xm Mon XX,XXXX
To Change Minute,Press (+)(-) &(Enter)
Current Time/Date HH:MM xm Mon XX,XXXX
To Change Month, Press(+)(-) & (Enter)
Current Time/Date HH:MM xm Mon XX,XXXX
To Change Day, Press (+)(-) & (Enter)
Current Time/Date HH:MM xm Mon XX,XXXX
To Change Year, Press (+)(-) & (Enter)
Front Panel Chilled Wtr Setpt:xxx.x f/c
Press (+)(-) to Change Setting