82 CVHE-CLD-1A
FastPak™ “Settings Group” Menu Record
Service Settings Group: Basic Setups
Menu Item Choices Default Design/Actual
1 Language English, Francais, Deutch,
Espanol, Nippon, Italiano,
Nederland, Portuguese,
Coded
English
2 Display Units English, SI XXX.X, XXX English
3 Decimal Places Displayed XXX.X
4 Display Menu Headings Enable, Disable Enable
5 Differential To Start Setpoint 1 to 10°F, 0.5 to 5.5 °C 5 °F, 2.8°C
6 Differential To Stop Setpoint 1 to 10°F, 0.5 to 55°C 5 °F, 2.8°C
7 Evap Pump Off Delay 0 to 30 Minutes 1 Minute
8 Printer Setups
Print Time Interval Enable, Disable Enable
Print on Time Interval 1 to 24 hrs. 8 hrs.
Print on Diagnostic Enable, Disable Enable
Number of Pre-Diag Reports 1 to 5 5
Diagnostic Report Interval 2 to 120 seconds S seconds
Printer, Baud Rate 300, 4800, 1200, 9600,
2400, 19,200
9600
Printer, Parity None, Odd, Even None
Printer, Data Bits 8,7 8
Printer, Stop Bits 1,2
Printer, Handshaking XON/XOFF, DTR, RTS,
None
XON/XOFF