Installation
SO-SVN038A-EN 11
Upgrading Display Firmware
Important: This firmware upgrade applies to existing,
reused black frame AdaptiView displays. Gray
frame displays are incompatible with Symbio
and must be replaced with the new black frame
display.
Display firmware download must be done
using a functional UC800 controller. If the
existing UC800 controller is not functional, a
substitute UC800 controller must be obtained.
Download can not be done with a Symbio
controller. Use of a Symbio controller will result
in a loss of communication to the UC800, which
cannot be restored.
Upgrade the display firmware by completing the following
steps.
1. Connect your laptop to the USB port on the UC800 or on
the control panel.
2. Start Tracer® TU.
3. Click Utilities on top of TU and click File Transfer Utility.
4. Click Yes for the save file popup.
5. The File Transfer dialog box will appear. Deselect the
UC800 and select the Tracer AdaptiView.
6. Click Next.
7. In the next dialog box, click Browse button and navigate to
the display firmware file, then click Open to select the file
and then click Next.
Notes:
• Obtain TD display firmware from the Trane
Commercial Downloads page, Symbio™ 800 section.
• Recommended firmware location:
C:\ProgramData\Trane\Tracer TU\Firmware\TD12
Figure 4. Tracer AdaptiView selection