Start-Up
WSHP-SVX01L-EN 87
GEVE042
042 (60 Hz)
036 (50 Hz)
68 7.8 122-140 242-308 12-15 20-26 122-140 318-404 9-12 31-41
042 (60 Hz)
036 (50 Hz)
68 9.8 121-140 234-298 9-12 20-26 126-144 321-409 7-9 31-42
042 (60 Hz)
036 (50 Hz)
75 7.8 123-141 267-340 12-15 20-25 136-156 331-422 10-13 33-44
042 (60 Hz)
036 (50 Hz)
75 9.8 122-141 259-330 9-12 20-26 140-161 336-427 8-10 34-45
042 (60 Hz)
036 (50 Hz)
86 7.8 126-144 307-390 11-15 19-25 160-184 355-452 11-14 38-49
042 (60 Hz)
036 (50 Hz)
86 9.8 125-144 299-380 9-12 19-25 166-190 359-457 9-12 39-50
042 (60 Hz)
036 (50 Hz)
95 7.8 127-147 345-439 11-14 18-24 — — — —
042 (60 Hz)
036 (50 Hz)
95 9.8 127-146 337-428 9-11 18-24 — — — —
GEHE048
048 (60 Hz)
042 (50 Hz)
35 — — — — — 74-85 263-334 6-8 20-29
048 (60 Hz)
042 (50 Hz)
35 — — — — — 76-87 265-337 5-6 20-29
048 (60 Hz)
042 (50 Hz)
45 9.0 120-138 184-234 13-16 23-29 85-98 273-348 7-9 23-32
048 (60 Hz)
042 (50 Hz)
45 11.2 120-138 176-225 10-13 23-29 87-100 275-350 6-7 23-33
048 (60 Hz)
042 (50 Hz)
55 9.0 121-140 214-273 13-16 23-28 101-117 289-368 8-10 26-36
048 (60 Hz)
042 (50 Hz)
55 11.2 121-139 206-262 10-13 23-28 104-120 292-372 6-8 26-36
048 (60 Hz)
042 (50 Hz)
68 9.0 125-144 256-326 13-16 22-28 117-135 305-388 9-12 30-40
048 (60 Hz)
042 (50 Hz)
68 11.2 125-144 247-315 10-13 23-28 122-140 310-394 7-10 30-41
048 (60 Hz)
042 (50 Hz)
75 9.0 126-146 282-359 12-16 22-28 131-151 318-405 10-13 32-43
048 (60 Hz)
042 (50 Hz)
75 11.2 126-145 273-348 10-13 22-28 136-156 322-410 8-10 33-44
048 (60 Hz)
042 (50 Hz)
86 9.0 129-148 324-412 12-15 21-27 154-177 339-431 11-14 36-47
048 (60 Hz)
042 (50 Hz)
86 11.2 128-147 314-400 10-12 22-27 160-184 344-437 9-12 37-48
048 (60 Hz)
042 (50 Hz)
95 9.0 130-150 364-463 12-15 21-27 — — — —
048 (60 Hz)
042 (50 Hz)
95 11.2 130-149 354-451 10-12 21-27 — — — —
Table 49. Operating pressures in cooling/heating for GE units (continued)
Operating Data
Model No.
Entering
Water
Temp
(°F)
Water
Flow
(GPM)
Cooling Heating
Suction
Pressure
(psig)
Discharge
Pressure
(psig)
Water
Temp Rise
(°F)
Air Temp
Drop
(°F DB)
Suction
Pressure
(psig)
Discharge
Pressure
(psig)
Water
Temp
Drop (°F)
Air Temp
Rise
(°F DB)