RT-SVX073A-EN
137
Figure 92. 150 ton eFlex variable speed—circuit 1 and circuit 2 operating pressure curve (compressor at 100% and all
condenser fans ON) (standard capacity)
250
300
350
400
450
500
550
600
90 100 110 120 130 140 150 160 170 180
Discharge Pressure, PSIG
Sucon Pressure, PSIG
105
o
F Ambient
95
o
F Ambient
85
o
F Ambient
75
o
F Ambient
65
o
F Ambient
250
300
350
400
450
500
550
90 100 110 120 130 140 150 160 170 180
Discharge Pressure, PSIG
Sucon Pressure, PSIG
105
o
F Ambient
95
o
F Ambient
85
o
F Ambient
75
o
F Ambient
65
o
F Ambient
150 Ton eFlex Circuit 1, 50Hz
150 Ton eFlex Circuit 2, 50Hz
Components
Economizer and Exhaust Air Damper
Adjustment
Exhaust Air Dampers
Verify that the exhaust dampers (if equipped) close tightly
when the unit is off. Adjust the damper linkage as
necessary to ensure proper closure. An access panel is
provided under each damper assembly.
Outside Air and Return Air Damper
Operation
The outside air and return air damper linkage is accessible
from the filter section of the unit. The damper linkage
connecting the outside air dampers to the return air
dampers is preset from the factory in the number 1
position. Refer to Figure 93, p. 139 for the appropriate
linkage position for the unit and operating airflow (CFM).