Operation
35BAS-SVX08D-E4
Data
Type
Offset Point DescriptionFunction
Modbus
Index
10041 40 Transition contactor 1 ( 1 = ON, 0 = OFF) bit
10042 41 Reset relay 2 ( 1 = ON, 0 = OFF) bit
10047 46 Oil line solenoid valve 2,
female slide valve step load solenoid for 70-125 Ton ( 1 = ON, 0 = OFF) bit
10048 47 Transition contactor 2 ( 1 = ON, 0 = OFF) bit
10049 48 Reset relay 2 ( 1 = ON, 0 = OFF) bit
10054 53 Oil line solenoid valve 2,
female slide valve step load solenoid for 70-125 Ton ( 1 = ON, 0 = OFF) bit
10055 54 Transition contactor 2 ( 1 = ON, 0 = OFF) bit
10059 58 Unit type RTXA (1 = true) bit
10060 59 Circuit 2 oil bypass (1 = on) bit
10061 60 Circuit 1 oil bypass (1 = on) bit
10062 61 Circuit 2 reversed (1 = yes (heating), 0 = no) bit
10063 62 Circuit 1 reversed (1 = yes (heating), 0 = no) bit
10065 64 Informational warning (1 = active) bit
10066 65 Circuit 2 auto reset (1 = active) bit
10067 66 Circuit 1 auto reset (1 = active) bit
10068 67 Circuit 2 manual reset required (1 = active) bit
10069 68 Circuit 1 manual reset required (1 = active) bit
30001 0 Evaporator leaving water temperature Temperature
30002 1 Evaporator entering water temperature Temperature
30003 2 Condenser leaving water temperature Temperature
30004 3 Condenser entering water temperature Temperature
30005 4 Average % current for chiller Percentage
30006 5 Operating code None
30007 6 Last diagnostic code None
30008 7 Active chiller water/ice term setpoint Temperature
30009 8 Copy of function 2 binary points bitfield
30010 9 00h = 130-400 Ton RTAA (Intermediate screw),
01h = 70-125 Ton (General purpose screw) None
30011 10 00h = 130-400 Ton RTAA, 06h = 70-125 Ton None
30012 11 00h = 130-400 Ton RTAA (Required by the Remote Display) None
30013 12 CPM module software revision level None
30014 13 CSR module software revision level None
30015 14 Master EXV module software revision level None
30016 15 MSCP module # 1 software revision level None
30017 16 MSCP module # 2 software revision level None
30018 17 MSCP module # 3 software revision level None
30019 18 MSCP module # 4 software revision level None
Bit 2-0 = Number of compressors on unit
Bit 4-3 = Number of circuits on unit
Bit 6-5 = Manifolded pair identification
00h = AB/CD (4 CPRSR UNIT), AB/C (3 CPRSR UNIT), A/B (2 CPRSR UNIT)
01h, 10h, 11h = UNDEFINEDBit 7 = Water cooled unit (1 = Yes, 0 = No)
Bit 7 = Water cooled unit (1 = Yes, 0 = No)" bitfield
Bit 1-0 = 00h (Stop/reset), 01h (Auto/remote), 10h = Auto/Local
Bit 2 = Evaporator pump status (1 = ON, 0 = OFF)
Bit 3 = Night noise setback bit (1 = ON, 0 = OFF)
Bit 4 = Compressor running bit (1 = any compressor running)
Bit 5 = Alarm bit (1 = alarm)
Bit 6 = Actively ice making bit (1 = making ice)
Bit 7 = Max capacity bit (1 = max capacity)" bitfield
Analog
Inputs
4
Binary
Inputs
2
30020 19
30021 20
Unit
Table 14 - Continued

Table of Contents