EasyManua.ls Logo

Trane PIC - Page 76

Trane PIC
80 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Data Point Description
Table A - How to read Chiller Status in equipment data point lists
Chiller Status - bitfield
Item Register bit Description
Chiller Run Mode Bits 0-3
0 (0000) = Chiller Off
1 (0001) = Chiller in start mode
2 (0010) = Chiller in run mode
3 (0011) = Chiller in pre-shutdown mode
4 (0100) = Chiller in service mode
any others = not applicable
Chiller Operating Mode Bits 4-7
0 (0000) = Cooling mode
1 (0001) = Heating mode
2 (0010) = Free cooling mode
3 (0011) = Ice-making mode
any others = not applicable
Chiller in alarm Bit 8
1=Chiller has an active diagnostic that caused the chiller to be shutdown.
(These are shutdown alarms, not warnings.)
0=No shutdown alarms are present.
Chiller enabled Bit 9
1=Chiller is available to run or is currently running.
0=Chiller is not permitted to run.
Chiller local mode Bit 10
1=Chiller is in local mode. BAS is disabled in the Setpoint Source and the chiller will
ignore communications.
0=Chiller is not in local mode and network visible values may be changed remotely.
Chiller in limits Bit 11
1=Conditions may exist that prevent the chiller from reaching setpoint.
0=Chiller is not restricted from attempting to reach setpoint.
Chilled water flow Bit 12
1=Chilled water flow is detected
0=No chilled water flow is observed.
Condenser water flow Bit 13
1=Condenser water flow is detected.
0=No condenser water is observed.
Maintenance
BAS-SVX08D-E476

Table of Contents

Related product manuals