RT-SVX092A-EN
11
Wall Mounted Relative Humidity Sensor
(BAYSENS036*)
Field installed, wall mounted humidity sensor that
measures temperature and relative humidity. Relative
humidity input is used to control activation of
dehumidification
Duct Mounted Relative Humidity Sensor
(BAYSENS037*)
Field installed, duct mounted humidity sensor that
measures temperature and relative humidity. Relative
humidity input is used to control activation of
dehumidification.
Integrated Comfort System
(BAYSENS073*)
This sensor features remote zone sensing and timed
override with override cancellation. It is used with a Trane
Integrated Comfort™ building management system.
Integrated Comfort System
(BAYSENS074*)
This sensor features single setpoint capability and timed
override with override cancellation. It is used with a Trane
Integrated Comfort™ building management system.
Remote Zone Sensor (BAYSENS016*)
This bullet type temperature sensor can be used for outside
air (ambient) sensing, return air temperature sensing,
supply air temperature sensing, remote temperature
sensing (uncovered). Wiring procedures vary according to
the particular application and equipment involved. Refer to
the unit’s wiring diagrams for proper connections.
Remote Zone Sensor (BAYSENS077*)
This sensor can be used with BAYSENS106*, 108*, 110*,
800* Remote Panels. When this sensor is wired to a
BAYSENS800* Remote Panel, wiring must be 18 AWG
Shielded Twisted Pair (Belden 8760 or equivalent). Refer to
the specific Remote Panel for wiring details.
Thermostat
Room thermostats are delicate temperature sensing
controls. Their main function is to energize and de-energize
the heating or cooling circuit to maintain the temperature
setting you select.
Many thermostats contain a room thermometer to indicate
the approximate room temperature and a temperature
scale at the adjustment indicator to select the desired
indoor air temperature. In addition, most thermostats have
a selector mode switch with Heat, Off and Cool positions
and a fan switch with On and Off positions.
When the switch is positioned at Off your unit will not
operate in either the heat or cool modes. If the selector
switch is set at Heat the unit will automatically cycle on and
off to maintain the desired temperature setting. The unit will
also operate automatically when the selector switch is
positioned at Cool.
The fan selector switch can be used to operate the indoor
fan continuously by positioning it at On. When set to Auto
the fan will only operate when required during the heating
or cooling cycles.
To ensure that the thermostat operates properly, it must be
level and positioned to avoid the influence of such external
heat sources as lamps, televisions or other heat producing
appliances.
Notes:
Single zone VAV is designed to be used with a
zone sensor. If a unit is configured for Single
zone VAV operation but is connected to a
thermostat, the control will revert to multi-speed
(2-speed) indoor fan control and staged
compressor control. This drastically reduces
the energy savings available with this design.
eFlex™ is designed to be used with a zone
sensor. If a unit is configured for variable speed
compressor operation but is connected to a
thermostat, the control will revert to multi-speed
indoor fan control and staged compressor
control. This drastically reduces the energy
savings available with this design.
The unit must have a thermostat to operate.
BAYSTAT150
Three Heat/Two Cool Auto changeover digital
display thermostat. Seven day programmable
thermostat with night setback.
BAYSTAT152
Thermostat, programmable, touch screen, Three
Heat/Two Cool Auto changeover digital display
thermostat. Seven day programmable thermostat
with night setback.
BAYSTAT814
Smart Thermostat, programmable, touch screen,
Three Heat/Two Cool Auto changeover digital
display thermostat. Seven day programmable
thermostat with night setback and Time Override.
Can be stand alone or multi-thermosets managed
by mobile app.
High Temperature Sensor (FIAHTST001*)
This sensor connects to the Symbio™ 700 Emergency
Stop Input and provides high limit “shutdown” of the unit.
The sensor is used to detect high temperatures due to a
high thermal event in the air conditioning or ventilation
ducts. The sensor is designed to mount directly to the
sheet metal duct. Each kit contains two sensors. The return
air duct sensor (X13100040010) is set to open at 135ºF.
The supply air duct sensor (X13100040020) is set to open
at 240ºF. The control can be reset after the temperature
General Information

Table of Contents