Table 6. Chiller events/status descriptions
E
vent
/
Stat
e
D
escri
p
tio
n
A
larm - Latchin
g
This output is true whenever there is any active dia
g
nostic that requires a manual
reset to clear, that effects the Chiller, the Circuit, or an
y
of the Com
p
ressors on a
c
ircuit. This classi cation does not include informational dia
g
nostics.
A
l
a
rm - A
u
t
o
Rese
t
This output is true whenever there is any active dia
g
nostic that could automatically
c
lear, that effects the Chiller, the Circuit, or an
y
of the Com
p
ressors on a circuit.
This classi cation does not include informational dia
g
nostics. If all of the auto
resettin
g
dia
g
nostics were to clear, this output would return to a false condition.
A
l
a
r
m
This output is true whenever there is any dia
g
nostic effectin
g
any component,
whether latchin
g
or automatically clearin
g
. This classi cation does not include
informational dia
g
nostics.
W
arnin
g
This output is true whenever there is any informational dia
g
nostic effectin
g
any
c
omponent, whether latchin
g
or automatically clearin
g
.
Chiller Limit M
od
e This output is true whenever the chiller has been runnin
g
in one of the Unloadin
g
t
yp
es of limit modes
(
Condenser, Eva
p
orator, Current Limit or Phase Imbalance
L
imit) continuously for the last 20 minutes. A
g
iven limit or overlappin
g
of different
limits must be in effect continuously for 20 minutes prior to the output becomin
g
true. It will become false, if no Unload limits are
p
resent for 1 minute. The lter
prevents short duration or transient repetitive limits from indicatin
g
. The chiller
is considered to be in a limit mode for the
p
ur
p
oses of front
p
anel dis
p
la
y
and
a
nnunciation, only if it is fully inhibitin
g
loadin
g
by virtue of bein
g
in either the
hold” or “forced unload” re
g
ions of the limit control, excludin
g
the “limited
loadin
g
re
g
ion”. (In previous desi
g
ns, the “limit load” re
g
ion of the limit control
was included in the criteria for the limit mode call out on the front
p
anel and
a
nnunciation out
p
uts
)
C
ompressor Runnin
g
The output is true whenever any compressors are started or runnin
g
on the
c
hiller and false when no compressors are either startin
g
or runnin
g
on the chiller.
This status ma
y
or ma
y
not re ect the true status of the com
p
ressor in Service
P
um
p
down if such a mode exists for a
p
articular chiller.
Chiller He
ad
Press
u
re Relie
f
R
e
q
uest Rela
y
This relay output is ener
g
ized anytime the chiller is runnin
g
in one of the followin
g
modes; Ice Makin
g
Mode or Condenser Pressure Limit Control Mode continuously
for the duration s
p
eci ed b
y
the Chiller Head Relief Rela
y
Filter Time. The Chiller
H
ead Relief Relay Filter Time is a service setpoint. The relay output is de-ener
g
ized
a
n
y
time the chiller exits all above modes continuousl
y
for the duration s
p
eci ed b
y
the same Chiller Head Relief Rela
y
Filter Time.

Other manuals for Trane Tracer TD7

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Trane Tracer TD7 and is the answer not in the manual?

Trane Tracer TD7 Specifications

General IconGeneral
BrandTrane
ModelTracer TD7
CategoryController
LanguageEnglish

Related product manuals