18 BAS-SVX50F-EN
Installing the Tracer TD7 Display
Using the TD7 Portable Display
1. Locate the Tracer UC600 to be used with the TD7 display.
2. Remove the Ethernet and power cables from
the pouch of the TD7 portable carry case.
3. Connect the Ethernet cable to the display port on the Tracer UC600
. As an example, see Figure 3,
p. 14.
4. Connect the power cable to an a
vailable 2
4 VAC connection on the Tracer UC600. The TD7 will
start up in approximately 90 seconds.
Note: The TD7 Display draws 21 VA of power. Proper sizing of the transformer is required. See the
“Trace
r UC600 Installation, Operation, and Maintenance guide,” BAS-SVX45-EN for more
information on power budgeting.
Powering up the TD7 Display for the First Time
After completing the installation instructions in “Installing the Tracer TD7 Display,” p. 12, The TD7
display can be powered up.
Before applying power to the TD7, ve
rify the following:
The UC600 is powered up.
The Ethernet cable between the UC600 and the TD7 is securely attache
d.
The link light on the UC600 should be on stea
dy (solid green with a flashing activity light,
indicates good Ethernet communication).
Upon successful power up, the TD7 display will default to th
e configured home screen. The All
Points Report is the factory default.
Important: Do
no
t attempt to update the TD7 Display from a connection type other than a USB.

Table of Contents

Other manuals for Trane Tracer TD7

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Trane Tracer TD7 and is the answer not in the manual?

Trane Tracer TD7 Specifications

General IconGeneral
BrandTrane
ModelTracer TD7
CategoryController
LanguageEnglish

Related product manuals