VAV-SVX07B-EN 7
Overview
Specifications and Dimensions
Storage
Temperature: –48°F to 203°F (–44°C to 95°C)
Relative Humidity: Between 5% and 95% (non-condensing)
Operating
Temperature: –40°F to 185°F (–40°C to 70°C)
Humidity: Between 5% and 95% (non-condensing)
Input Voltage: 20.4–27.6 Vac (24, ±15% nominal), 50Hz to 60Hz
Mounting weight of controller: Mounting surface must support 0.80 lb. (.364 kg)
Environmental rating (enclosure): NEMA 1
Altitude: 9,842 ft. maximum (3,000 m)
Installation: U.L. 840: Category 3
Pollution: U.L. 840: Degree2
Housing Material:
Polycarbonate/ABS Blend
•UV protected
U.L. 94-5VA flammability rating
Mounting:
Mounts on EN 50 022 - 35 X 15 DIN rail that is included in the VAV unit control box when the UC400 is factory
mounted.
Agency Listing/Compliance
UL916 PAZX, Open Energy Management Equipment
UL94-5V, Flammability
•CE Marked
FCC Part 15, Subpart B, Class B Limit
AS/NZS CISPR 22:2006
VCCI V-3/2008.04
ICES-003, Issue 4:2004
Communications BACnet MS/TP, supports BACnet protocol ASHRAE 135-2004 and meets BACnet Testing Laboratory (BTL) as an Application Specific Controller
(ASC) profile device UL864/UUKL listed when installed and programmed in accordance with the Trane Applications Guide, BAS-APG019-EN.
*DIN Standard 43 880, Built-in Equipment for Electrical Installation. Overall Dimensions and Related Mounting Dimensions.
For mounting and clearance recommendations, refer to Tracer UC400 Programmable Controller Installation, Operation, and
Maintenance Manual (BAS-SVX20).
5.65 in. (143.5 mm)
[*8 units]
2.37 in
(60.1 mm)
1.89 in
(48 mm)
1.79 in
(45.4 mm)
4.00 in
(101.6 mm)

Table of Contents

Other manuals for Trane Tracer UC400

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Trane Tracer UC400 and is the answer not in the manual?

Trane Tracer UC400 Specifications

General IconGeneral
MountingDIN Rail
Operating Temperature-40°F to 158°F (-40°C to 70°C)
Enclosure RatingIP20
Controller TypeProgrammable
Communication ProtocolBACnet MS/TP
Power Supply24 VAC
Power Consumption10 VA
Humidity Range5% to 90% RH non-condensing
Supply Voltage24 VAC/VDC