EasyManua.ls Logo

Trane Tracer ZN517 - Power and Operating Environment

Trane Tracer ZN517
111 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Chapter 1 Overview and specifications
2 CNT-SVX12C-EN
Metal-cover model dimensions
For complete dimensional drawing, see Figure 2 on page 3.
Height: 9.0 in (25 mm)
Width: 10.37in. (263 mm)
Depth: 2.25 in. (58 mm)
Clearances
For wiring, ventilation, and maintenance, provide the following minimum
clearances for the module:
Plastic-cover model
(see Figure 1 on page 3)
Front: 4.0 in. (102 mm)
Each side: 1.0 in. (25 mm)
Top and bottom: 4.0 in. (102 mm)
Metal-cover model
(see Figure 2 on page 3)
Front: 24.0 in. (610 mm)
Each side: 2.0 in. (51 mm)
Top and bottom: 1.0 in. (25 mm)
Power
The transformer must meet the following minimum requirements for the
controller and its output devices:
19–30 Vac (24 Vac nominal)
50/60 Hz
9 VA and 12 VA maximum per binary output utilized
Operating environment
Operate a Tracer ZN517 unitary controller in an indoor environment that
meets the following requirements:
Temperature: From –40°F to 160°F (–40°C to 70°C)
Relative humidity: From 5–90%, noncondensing

Table of Contents