Chapter 1 Overview and specifications
4 CNT-SVX12C-EN
Storage environment
If you are storing a Tracer ZN517 unitary controller for a substantial
amount of time, store it in an indoor environment that meets the
following requirements:
Temperature: From –40° to 185°F (–40° to 85°C)
Relative humidity: From 5–95%, noncondensing
Agency listing/compliance
CE—Immunity: EN50082-2:1995
EN61000-6-2:1999
CE—Emissions: EN61000-3-2:1995
EN61000-3-3:1995
EN50081-1:1992 (CISPR 22)
EN55011:1998, Class B
UL and C-UL 916 listed:
Energy management equipment
UL 94-5V (UL flammability rating for plenum use)
FCC Part 15, Class A, CFR 47
Factory default temperature setpoints
The Tracer ZN517 unitary controller relies on a number of temperature
setpoints to control HVAC equipment. Table 1 gives the factory defaults
for these setpoints, which can all be edited with the Rover service tool or a
BAS.
Table 1. Factory default temperature setpoints
Setpoints
Factory defaults
°F (°C)
Default setpoints
Occupied cooling 74.0°F (23.3°C)
Occupied standby cooling 78.0°F (25.6°C)
Unoccupied cooling 85.0°F (29.4°C)
Occupied heating 71.0°F (21.7°C)
Occupied standby heating 67.0°F (19.4°C)
Unoccupied heating 60.0°F (15.6°C)
Occupied setpoint limits
Cooling setpoint high limit 110.0°F (43.3°C)
Cooling setpoint low limit 40.0°F (44.4°C)