EasyManuals Logo

Trane Tracer ZN517 User Manual

Trane Tracer ZN517
111 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Page #54 background imageLoading...
Page #54 background image
Chapter 6 Sequence of operations for the 4-cool configuration
42 CNT-SVX12C-EN
Discharge air tempering
Discharge air tempering (also called supply air tempering) prevents occu-
pant discomfort caused by cold outside air being brought into a space
through the outside air damper. This is an important feature in cold cli-
mates because the outside air damper is never fully closed for ventilation
purposes. Discharge air tempering starts when:
The controller is in heating mode.
The space is otherwise satisfied (no heating or cooling required).
Ventilation air is passing through the unit
The discharge air temperature falls 10°F (5.6°C) below the occupied
heating setpoint.
Tempering stops when the occupied heating setpoint is exceeded. To
enable this function, use the Rover service tool to select Supply Air Tem-
pering Enabled.
Demand control ventilation
The Tracer ZN517 unitary controller modulates the outside air damper
position in direct response to the CO
2
level, regulating the amount of out-
door air allowed to enter. This function is referred to as demand control
ventilation. Demand control ventilation requires that the two triac (3-
wire floating point) outputs be used to control the damper actuator. The
minimum damper position will increase as CO
2
levels rise above
500 ppm. The function executes with a 3-minute loop time to allow time
for the sensor to respond.
To enable this function, use the Rover service tool to configure the Tracer
ZN517 as follows:
Configure AI1 as a carbon dioxide sensor
Enter a minimum CO
2
level (Control Point)
(factory default: 500 ppm).
Enter a maximum CO
2
threshold (Threshold)
(factory default: 1500 ppm).
When the CO
2
level reaches the threshold, the minimum position is
100% open.
Unit protection strategies
The following strategies are initiated when specific conditions exist in
order to protect the unit or building from damage:
Filter maintenance timer
Fan off delay
Fan status

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Trane Tracer ZN517 and is the answer not in the manual?

Trane Tracer ZN517 Specifications

General IconGeneral
BrandTrane
ModelTracer ZN517
CategoryController
LanguageEnglish

Related product manuals