RT-SVX34C-EN 33
Installation Electrical
TC/TE/
YC*600
208/60/3 187-229
2/13,1/
15
50.5/56.0 315/351
10.0
15.0
20.0
29.0
40.7
56.1
4 1.1 7.0 1 2 1.5 5.4
230/60/3 207-253
2/13,1/
15
50.5/56.0 315/351
10.0
15.0
20.0
25.2
37.8
49.4
4 1.1 7.0 1 2 1.5 5.4
460/60/3 414-506
2/13,1/
15
23.0/27.5 158/197
10.0
15.0
20.0
12.6
18.9
24.7
4 1.1 3.5 1 2 1.5 2.7
575/60/3 517-633
2/13,1/
15
19.0/23.0 136/146
10.0
15.0
20.0
10.1
15.1
19.6
4 1.1 2.8 1 2 1.5 2.2
Notes:
1. All customer wiring and devices must be installed in accordance with local and national electrical codes.
2. 100% Power Exhaust is with or without Statitrac™.
Table 7. 27½-50 Ton Electrical Service Sizing Data—60Hz1
Fan Motors
Model
Electrical
Characteristics
Allowable
Voltage
Range
Compressor Supply Condenser Exhaust
No/Ton
RLA
(Ea.)
LRA
(Ea.) HP FLA No HP
FLA
(Ea.) 50%
100%
2
HP
FLA
(Ea.)
No.
Table 8. Electrical Service Sizing Data — Crankcase Heaters — (Heating Mode Only)—60Hz
Nominal
Unit Size
(Tons)
FLA Add
Unit Voltage
200 230 460 575
27½ - 351111
40, 502211