34 RT-SVX34C-EN
Installation Electrical
Table 9. Electrical Service Sizing Data—50Hz
Model
Electrical
Characteristic
s
Compressor
Fan Motors
Supply Condenser
1
Exhaust
No/Ton
RLA
(Ea.)
LRA
(Ea.) HP(kW) FLA No. HP(kW)
FLA
(Ea.)
50%
100%
4
HP
(kW)
FLA
(Ea.)No.
TC/TE/YC*275 380-415/50/3 1/10, 1/11 21.0/23.0 147/ 158 7.5 (5.6)
13.6/
14.1
3 .75 (.56) 4.4 1 2
.75
(.56)
1.7
10 (6.8)
16.0/
15.5
TC/TE/YC*305 380-415/50/3 2/11 23.0 158 7.5 (5.6)
13.6/
14.1
3 .75 (.56) 4.4 1 2
.75
(.56)
1.7
10 (6.8)
16.0/
15.5
TC/TE/YC*350 380-415/50/3 1/11, 1/12 23.0/27.5 158/ 197 7.5 (5.6)
13.6/
14.1
3 .75 (.56) 4.4 1 2
.75
(.56)
1.7
10 (6.8)
16.0/
15.5
15 (10.5)
24.0/
26.0
TC/TE/YC*400 380-415/50/3 1/11, 1/17 23.0/34.0 158/ 215 10 (6.8)
16.0/
15.5
4 .75 (.56) 4.4 1 2
1.0
(.75)
2.5
15 (10.5)
24.0/
26.0
TC/TE/YC*500 380-415/50/3 2/11, 1/12 23.0/27.5 158/ 197 10 (6.8)
16.0/
15.5
4 .75 (.56) 4.4 1 2
1.0
(.75)
2.5
15 (10.5)
24.0/
26.0
20 (12.8)
29.0/
28.0
Notes:
1. All condenser fan motors are single phase.
2. All customer wiring and devices must be installed in accordance with local and national electrical codes.
3. Allowable voltage range for the 380V unit is 342-418V, allowable voltage range for the 415V unit is 373-456.
4. 100% Power Exhaust is with or without Statitrac
Table 10. Electrical Service Sizing Data — Crankcase Heaters — (Heating Mode Only)—50Hz
Nominal
Unit Size
(Tons)
FLA Add
Unit Voltage
380 415
23 - 29 1 1
33 - 42 1 1

Table of Contents