System Specifications
Table 1 lists the system specifications of the Triacta GATEWAY
Table 1: Triacta GATEWAY specifications
Height: 15.52 in. (39.4 cm) Width: 12 in. (38.9 cm) Depth: 2.125 in. (9.0 cm)
8.77 lb (3.98 kg) - Fully configured
Sense voltages
Vref1 and Vref2
90V to 300V 50/60Hz
1W+N+Protective Earth
2W+N+Protective Earth Wye
3W+N+Protective Earth Wye
3W+Protective Earth Delta
90V to 300V AuxA-AuxN, 15 watts max, 50/60 Hz
3.15A, 500V Slow Blow 5 x 20mm
Current Sensing Inputs (All CTs must be UL recognized/listed.)
Electrical Metering Accuracy
Measurement Canada Approved in accordance with EG07
U.S.A. ANSI C12.20 Class 0.5
IEC 62053-22 Class 5S for EU
(Accuracy compliant when used with 0.3% CTs)
UL/CSA 61010 Ed3 300V CAT II
• CANADA - CAN/CSA-C22.2 No. 61010-1-12 (IEC 61010-1:2010, MOD)
• USA - UL61010-01 (IEC 61010-1:2010, MOD)
Dry Contact form A and solid-state form A compatible
Internal 3.3V pull-up
5Vdc pulse required for Solid State
Maximum frequency 200 Hz
Minimum pulse width 2.0 ms
Meter Head Unit Communications Interfaces
10/100BaseT 802.3-2002; RJ45