13. Technical Data
57
Greenflame Specification
GREENFLAME
55
GREENFLAME
85/100/125
GREENFLAME
199
Width A
mm
1552
1690
1900
Height B
mm
1540
1940
1940
Depth C
mm
1178
1323
1500
Fuel Hopper Capacity
kgs
152
125
125
Boiler Flue Pipe Diameter
mm
152
200
200
Dry Weight Empty
kgs
750
1950
1000
Water Content
litres
160
410
280
Operating Temperature - Water
°C
50 - 85 °C
50 - 85 °C
50 - 85 °C
Nominal Output
kW
16.5 - 55
27 - 125
55 - 199
Nominal Fuel Input
kW
TBC
138
TBC
Reduced Fuel Input (30%)
kW
TBC
30
TBC
Efficiency Nom. Input (EN303-5) *
%
90
90.4
90
Smoke Temp at Nominal Power
°C
165.3
183
180
Smoke Temp at Reduced Power
°C
106.2
110
110
Min. Required Draft
Pa
10
10
10
Exhaust mass flow
g/s
15.7 28.7
43 - 102
Recommended Operating Pressure
bar
1.5
1.5
1.5
Maximum Operating Pressure
Bar
3
3
3
Water Flow Connection
Inch
1.5”
2"
2”
Water Return Connection
Inch
1.5”
2"
2”
Boiler Drain
Inch
1”
1"
1”
Boiler Safety Thermostat Setting
°C
105
105
105
Boiler Class
Class
Class 3
Class 3
Class 3
Flue Size
6”
8”
8”
Boiler Power Requirement
230V - 50 Hz / 15.3 Amp
Max. Electrical Consumption
kW
</= 1.5
</= 1.5
</= 1.5
Line Voltage Fuse Protection
(Controller)
Amp
6.3
6.3
6.3
PCB Fuse Protection
Amp
15.3
15.3
15.3
* EN303-5 - Heating boilers for solid fuels, hand and automatically fired, nominal
heat output of up to 300kW

Related product manuals