3.4 Power Requirement
. Power and ground
Main power input 3 phase 415V with Neutral and earth
32 Amps per phase
Single Phase Not Required
7. Notes on installing power source and grounding work
(1) Do not co-use power cable with other machines. Provide an independent power
line for this Machine.
(4) Power cable’s external terminals must be protected by a fuse or breaker.
(5) The grounding resistance should be less than 50Ω.
(6) Grounding line color is yellow-green.
Graphic demonstration of machine grounding:
Fig. 1: Single set grounding
Fig. 2: Multi sets grounding