Appendix B
106
Object Type
Device
Instance
*Units
Description
Writable
Notes and Range
Object
Value
Multi-State
Value
11
Room 1 Mode
Y
1 Positive
2 Negative
3 No Isolation
Multi-State
Value
12
ACH Duct
Y
1 Supply
2 Exhaust
3 Off
Multi-State
Value
13
No Isolation Control
Type
Y
1 Position
2 Flow
3 Pressure
Multi-State
Value
14
Anteroom Mode
Y
1 Positive
2 Negative
3 No Isolation
Multi-State
Value
16
Status Index
1 Normal
2 Room 1 Negative
Low Alarm
3 Room 1 Negative
High Alarm
4 Room 1 Positive
Low Alarm
5 Room 1 Positive
High Alarm
6 Low Exhaust Alarm
7 Low Supply Alarm
8 Low Temperature Alarm
9 High Temperature Alarm
10 Low RH Alarm
11 High RH Alarm
12 Anteroom Negative
Low Alarm
13 Anteroom Negative
High Alarm
14 Anteroom Positive
Low Alarm
15 Anteroom Positive
High Alarm
20 Data Error
Multi-State
Value
17
Device Type
1 RPC30
Multi-State
Value
18
Units Value
Y
1 in. W.C., cfm, F
2 Pa, lps, C
3 Pa, CMH, C
* The units are based on the value of the Units Value object. When the Units Value is set to 1, the units are in English
form. When the Units Value is set to 2 or 3, the units are metric. English is the default value.

Table of Contents

Other manuals for TSI Instruments PRESSURA RPC30

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the TSI Instruments PRESSURA RPC30 and is the answer not in the manual?

TSI Instruments PRESSURA RPC30 Specifications

General IconGeneral
BrandTSI Instruments
ModelPRESSURA RPC30
CategoryController
LanguageEnglish

Related product manuals