6. SPECIFICATION OF INPUTS AND OUTPUTS
6.1.4.2 Vision 307Plus
Supply current characteristics for the Vision 307Plus device.
Symbol Parameter Note Typ Max Unit
I
BAT+ idle
Supply current at V
BAT+
= 8 V 1 1200 1300 mA
I
BAT+ idle
Supply current at V
BAT+
= 12 V 1 750 mA
I
BAT+ idle
Supply current at V
BAT+
= 24 V 1 400 mA
I
BAT+ STBY
Standby supply current at V
BAT+
= 12 V, 25
○
C 2 110 µA
Note 1 Idle mode refers to an operational state where there are no external loads, i.e., the Linux
command line runs with no additional application, or CPU-/GPU-load.
Note 2 Terminal 15 is off, device is shut down, and RTC capacitor is fully loaded
6.2 Negative power supply (BAT-)
6.2.1 Pinout
Connector Pin no. Function
C1 1, 2 Battery power supply input (BAT-)
6.2.2 Functional description
The pin for negative power supply. Always use all pins on the connector to distribute the current load.
6.2.3 Maximum ratings
Symbol Parameter Min Max Unit
I
BAT-max
Permanent supply current at V
BAT-
= 8 V, 25
○
C 2.5 A
6.3 Ignition on switch input (Terminal 15)
6.3.1 Pinout
Connector Pin no. Function
C1 18 Terminal 15 Input
6.3.2 Functional description
Terminal 15 switches the power supply of the Vision 307 device.