Operating
Evaluating process input data
108
Hans Turck GmbH & Co. KG | T +49 208 4952-0 | F +49 208 4952-264 | more@turck.com | www.turck.com
10 Operating
10.1 Evaluating process input data
Word
no.
Bit no.
15 14 13 12 11 10 9 8 7 6 5 4 3 2 1 0
Basic
0x00 - - - - DVS3 DVS2 DVS1 DVS0 - - - - IOL3 IOL2 IOL1 IOL0
IO-Link process input data
0x01
0x10
IO-Link port 1,
structure depends on the channel parameterization (0…32 byte per channel)
0x11
0x20
IO-Link port 2,
structure depends on the channel parameterization (0…32 byte per channel)
0x21
0x30
IO-Link port 3,
structure depends on the channel parameterization (0…32 byte per channel)
0x31
0x40
IO-Link port 4,
structure depends on the channel parameterization (0…32 byte per channel)
Diagnostics
DX channels/VAUX
0x41 - - - - ERR
DX3
ERR
DX2
ERR
DX1
ERR
DX0
- - - - ERR
VAUX
1 ch3
ERR
VAUX
1 ch2
ERR
VAUX
1 ch1
ERR
VAUX
1 ch0
IO-Link port 1
0x42 GEN-
ERR
OVL VHIG
H
VLO
W
ULVE LLVU OTM
P
PRME
RR
EVT1 EVT2 PDIN
V
HWE
RR
DSER
R
CFGE
RR
PPE -
0x43 IO-Link port 2, assignment similar to port 1
0x44 IO-Link port 3, assignment similar to port 1
0x45 IO-Link port 4, assignment similar to port 1
IO-Link Events
0x46 Port (1st Event) Qualifier (1st Event)
0x47 Event Code low byte (1st Event) Event Code high byte (1st Event)
0x64 Port 16th Event) Qualifier (16th Event)
0x65 Event Code low byte (16th Event) Event Code high byte (16th Event)
Module status (status word)
0x66 - FCE - - - COM V1 - - - - - - - - DIAG