Commissioning
Commissioning an IO-Link device with IO-Link V1.1
24
Hans Turck GmbH & Co. KG | T +49 208 4952-0 | F +49 208 4952-264 | more@turck.com | www.turck.com
8.4 Commissioning an IO-Link device with IO-Link V1.1
The data storage of the master should be cleared before a device with a different device type is
connected to an IO-Link port which has already been used before.
The data storage memory of the master can be deleted in two ways:
n Reset the master to factory settings.
n Delete the data storage memory using the parameter Data storage mode.
Reset the master to factory settings via DTM
From the Factory settings drop-down menu, select Set to factory settings.
Load the parameter changes into the device.
a The DTM resets the device automatically.
Fig.19: Reset device to factory settings via DTM (example)
Connect the IO-Link V1.1 device.
a The LED IOL at the IO-Link port is green, IO-Link communication active.