Parameterizing and Configuring
Parameters
96
Hans Turck GmbH & Co. KG | T +49 208 4952-0 | F +49 208 4952-264 | more@turck.com | www.turck.com
9 Parameterizing and Configuring
9.1 Parameters
The device has 2 bytes of module parameters, 16 bytes each of IO-Link port parameters and 8
bytes of parameters for VAUX1 monitoring.
Word no. Bit no.
15 14 13 12 11 10 9 8 7 6 5 4 3 2 1 0
Basic
0x00 - - - - - - - - - - - - SRO
ch3
SRO
ch2
SRO
ch1
SRO
ch0
IO-Link port 1
0x01 Cycle time GSD Activ-
ate
quick
start-
up
Data storage
mode
Operation mode
0x02 - Mapping
PCDO
Mapping
PDIN
Deactivate
diag.
PDIN
invalid
Rev.
0x03…
0x04
- - - - - - - - -
0x05 Vendor ID (MSB) Vendor ID (LSB)
0x06 Device ID Device ID (LSB)
0x07 Device ID (MSB) Device ID
0x08 - - - - - - - - - - - - - - - -
IO-Link port 2
0x09…
0x10
Assignment similar to IO-Link port 1 (word 0x02…0x09)
IO-Link port 3
0x11…
0x18
Assignment similar to IO-Link port 1 (word 0x02…0x09)
IO-Link port 4
0x19…
0x20
Assignment similar to IO-Link port 1 (word 0x02…0x09)
VAUX monitoring
0x21 - - - - - - VAUX1 pin
(ch1)
- - - - - - VAUX1 pin2
(ch0)
0x22 - - - - - - VAUX1 pin8
(ch3)
- - - - - - VAUX1 pin6
(ch2)