Commissioning
Commissioning the Device in Modbus TCP
54
Hans Turck GmbH & Co. KG | T +49 208 4952-0 | F +49 208 4952-264 | more@turck.com | www.turck.com
Register 0x113C and 0x113D: Restore Modbus-Connection-Parameters
Registers 0x113C and 0x113D serve for resetting the parameter-register 0x1120 and 0x1130 to
0x113B to the default settings. The service resets the parameters without saving them.
Procedure:
Write 0x6C6F to register 0×113C.
To activate the reset of the registers, write 0x6164 ("load") within 30 seconds in register
0x113D. Both registers can also be written with one single request using the function
codes FC16 and FC23.
a The parameters are reset tot default values.
Save changes via a subsequent Save service.
Register 0x113E and 0x113F: Save Modbus-Connection-Parameters
Registers 0x113E and 0x113F are used for the non-volatile saving of parameters in registers
0x1120 and 0x1130 to 0x113B.
Procedure:
Write 0x7361 to register 0×113E.
Write 0x7665 ("save") within 30 seconds in register 0x113F to activate the reset of the re-
gisters. Both registers can also be written with one single request using the function
codes FC16 and FC23.
a The parameters are saved.
8.8.3 Data width
Module Process input Process output Alignment
TBEN-S2-4IOL 208 byte 132 word by word