EasyManua.ls Logo

turck FEN20-4IOL - Product Description; Device Overview and Dimensions; Device Properties and Features

turck FEN20-4IOL
129 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
V01.00 | 2019/12
15
5 Product Description
The devices are designed in protection class IP20.
The FEN20-4IOL IO-Link Master Module has four IO-Link ports for connecting IO-Link devices.
The four IO-Link channels can be parameterized independently of each other and operated
either in IO-Link mode, in SIO mode (DI) or as universal DXP channels.
With Turck's "Simple IO-Link Device Integration (SIDI)", IO-Link devices can be directly integ-
rated into PROFINET via the GSDML file of the Devices.
If the IO-Link channels are used as DXP channels, they are freely usable as input or output.
For the connection of IO-Link devices and digital sensors and actuators four 10-pole terminal
connector is provided. The power supply connectors are designed as 3-pole terminal con-
nector.
5.1 Device overview
30 [1.18]
19.5 [0.77]
55 [2.17]
44.5 [1.75]
62.5 [2.46]
Fig.4: Dimensions FEN20-4IOL
5.2 Properties and features
n Fibre-glass reinforced housing
n Shock and vibration tested
n Protection class IP20
n Terminal connector
n Multiprotocol functionality: PROFINET Device, EtherNet/IP Device, Modbus TCP Slave
n PROFINET:
Conformance Class B PA
Simple IO-Link Device Integration (SIDI)
Conformance according to PROFINET specifikation V2.35
System redundancy S2, network load class 3
n EtherNet/IP:
Support ot the IO-Link Parameter Object for asynchronous services (IO-Link CALL)
Predefined in- and oputput assemblies
n Modbus TCP:
Modbus interface for asynchronous access via dta streams

Table of Contents