V01.00 | 2019/12
115
10.4.3 PROFINET diagnostics
Module diagnostics
(slot 0 according to configuration tool)
PROFINET Diagnostics
Error code Channel
Undervoltage V1 0x0002 0
Undervoltage V2 0x0002 1
VAUX1/VAUX2 diagnostics
(slot 1, according ot configuration tool)
PROFINET Diagnostics
Error code Channel
Overcurrent VAUX1 (pin 3) 0x0100 0
Overcurrent VAUX1 (pin 5) 0x0101
Overcurrent VAUX1 (pin 7) 0x0102
Overcurrent VAUX1 (pin 9) 0x0103
IO-Link port diagnostics PROFINET Diagnostics
IO-Link port 1
(Slot 2, according to configuration tool)
Error code Channel
Undervoltage (VLOW) 0x0002 0
Overcurrent (VHIGH) 0x0003
Overload (OVL) 0x0004
Over temperature (OTMP) 0x0005
Wrong or missing device (CFGER) 0x0006
Upper limit value exceeded (ULVE) 0x0007
Lower limit value underrun (LLVU) 0x0008
Data storage error (DSER) 0x0009
Process input data invalid (PDINV)
Maintenance events (EVT1)
Out of specification error (EVT2)
Port parameterization error (PPE)
Parameterization error (PRMER) 0x0010
Hardware error (HWER) 0x0015
IO-Link port 2
(Slot 3, according to configuration tool)
Similar to port 1 2
IO-Link port 3
(Slot 4, according to configuration tool)
Similar to port 1 4
IO-Link port 4
(Slot 5, according to configuration tool)
Similar to port 1 6