Connecting
Connecting IO-Link devices and digital sensors and actuators
20
Hans Turck GmbH & Co. KG | T +49 208 4952-0 | F +49 208 4952-264 | more@turck.com | www.turck.com
7.3 Connecting IO-Link devices and digital sensors and actuators
The device has a 10-pole terminal screw connector for connecting IO-Link devices and digital
sensors and actuators. The maximum tightening torque is 0.5 Nm.
Fig.12: Terminal screw connector for connecting IO-Link devices and digital sensors and actu-
ators
NOTICE
Wrong supply of IO-Link devices
Damage to the electronics
Only supply IO-Link devices with the voltage provided at the 10-pole terminal
screw connector.
Connect IO-Link devices and digital sensors and actuators according to the pin assign-
ment.
1 = V1 –
2 = C/Q 1
3 = V1+ 1
4 = C/Q 2
5 = V1+ 2
6 = C/Q 3
7 = V1+ 3
8 = C/Q 4
9 = V1+ 4
10 = V1-
1 2 3 4 5 6 7 8 9 10
Fig.13: Pin assignment